Configuring the Trigger-Action Feature
Disabling Rules 11-19
X To display information about rules
Use the show trigger-action rule characteristics
command:
Example Rule_ACTurnOnRule7:0 >>show trigger-action rule name
ACTurnOnRule7 characteristics
Figure 11.3 shows a sample Trigger Information Screen.
Figure 11.3 Rule Information Screen
X To turn off an outlet based on a temperature
sensor reading
1. Execute the config trigger command at the
InReach:0 >> prompt:
Example InReach:0 >>config trigger
2. Execute the following command at the Trigger Action:0 >>
prompt:
Example Trigger Action:0 >> trigger name check4-temp
3. Execute the following command at the Trigger_check4-
temp:0 >>
prompt:
Example Trigger_check4-temp:0 >>temperature port 5 > 25 cel
hysteresis 3
where 3 is the tolerance level in degrees.
Then enter:
Example Trigger_check4-temp:0 >>exit
4. Execute the following command at the Trigger-action:0 >>
prompt:
Example Trigger Action:0 >>action name temp-ac-power-off
5. Execute the following commands at the Action_temp-ac-
power-off:0 >>
prompt:
Examples Action_temp-ac-power-off:0 >>command outlet 11:5 off
Action_temp-ac-power-off:0 >>exit
Rule Name: ACTurnOnRule7
State: enabled
Trigger Name: TempPort3GT34 Type: Temperature (F)
Action Name: TurnOnAC7 Command: outlet 5:7 on
You must
have port 5
configured for
sensor.