15-24 Using the Analog Input Commands
LX Series Configuration Guide
Using the Analog Input Commands
This section explains how to configure the analog input
commands, including the following:
Naming Analog Inputs
Configuring an Analog Input Description String
Defaulting the Description for an Analog Input
Resetting Analog Inputs to the Defaults
Resetting the Analog Input Name to Its Default
Enabling and Disabling the Analog State
Configuring Analog Calibration
Naming Analog Inputs
The default name for an analog input is canonically derived from
the port number, slot number and point number. For example,
the default name for the 8th analog input on the 2nd slot of the
HDAM being managed by port 5 is
5_2_8.
X To configure by default name or by physical location
on the HDAM
Use the following command syntax:
Syntax hdam analog <analog_name> name <new_name>
X To configure a descriptive name for any analog input
in the LX-7204T/7304T
Use the following Privileged command syntax:
Syntax hdam analog port <port_number> slot <slot_number> point
<
point_number> name <new_name>
where
You can use
each point
name after on
the LX. You
can’t use the
same name on
multiple ports,
slots, or points.
analog_name Name of the analog input to rename.
new_name New analog name to assign to the analog input. The
name must start with a letter, and the remainder of the
name can contain only letters and/or numbers and/or
underscores.